CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
RATINGS:
Input: 100-240 V ac, 10 A, 50/60 Hz
Output: 24 V dc, 25 A
Notes:
1. Maximum operating ambient temperature is 60 °C.
2. Maximum operating relative humidity 96%, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing
conditions before application of power.
SAFETY COMPLIANCE STANDARDS: All models are Certified to be in compliance with the
applicable requirements of UL 2601-1 2
nd
Edition, CSA 22.2 No. 601.1-M90, IEC 601-1, and
EN 60601-1: A2 1995.
CLASSIFICATION:
(5.1) Protection against electric shock = Class I
(In accordance with
sub- clause 5 of
(5.2) Degree of protection against electric shock = Not acceptable for applied
part without additional isolation (contact factory for details)
IEC 601-1) (5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic
mixture with air, oxygen, or nitrous oxide. This evaluation is to be made on the
end equipment by the OEM.
(5.6) Mode of operation = Continuous
WARNING! RISK OF FIRE! SHOCK HAZARD!
Dangerous voltages are present on some components, printed wiring traces and heatsinks.
GROUNDING: The ground terminal, J1 Pin 3, should be bonded to Protective Earth in the end
application. However, using this terminal for the end product protective earthing terminal is not
recommended. A separate dedicated protective earthing point should be used.
FUSING: External fuses for both Line and Neutral must be provided when the host equipment uses a
Power Supply Cord. For permanently installed equipment the neutral conductor shall not be fused.
Recommended fuse value is T 12 A 250 V. The fuses must meet the requirements of UL 2601-1, CSA
22.2 No. 601.1, IEC 601-1, and EN 60601-1 and be acceptable for the country in which the host
equipment is to be installed. A blown fuse is an indication of catastrophic failure of circuit
component(s). Repair must be performed by Condor authorized personnel.
OUTPUTS: Either the + or - output should be connected to Protective Earth in the end application.
The output is intended for Protectively Earthed Signal Output and Intermediate Circuits only. The
output is not acceptable for patient connection without additional isolation. The DC output is SELV
under normal and single fault conditions.
41-35163-0001 Rev. A 9/24/01
Page 1 of 2
GPFM600-24
INSTALLATION INSTRUCTIONS
Vue de la page 0
1 2

Résumé du contenu

Page 1 - INSTALLATION INSTRUCTIONS

CONDOR DC POWER SUPPLIES INC. 2311 STATHAM PKWY OXNARD, CA 93033 + 805-486-4565 RATINGS: Input: 100-240 V ac, 10 A, 50/60 Hz Output: 24 V dc,

Page 2 - EXPLANATION OF SYMBOLS

OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some applications where an overvoltage condition co